Data Sheet for Product
Page 2 of 3
Siemens Industry, Inc.
Specifications
Dimensions
TIE
4" W × 5" L × 1-1/2" H
(102 mm × 127 mm × 38 mm)
Power Pack
2" W × 2-1/2" L × 1-3/5" H
(51 mm × 64 mm × 41 mm)
DC Power Cord
6 feet (1.8 m)
Input Voltage
TIE, 115 Volt
102 Vac to 132 Vac,
60 Hz @ 100 mA
TIE, 230 Volt
200 Vac to 250 Vac,
50 Hz @ 50 mA
Trunk 1 and Trunk 2 levels
per EIA RS-485
Termination
Switch selectable
8200 W pull up/down or
120 W End of Line
Bit Rates
1200, 4800, 9600, 19200,
38400, 57600, and 115200 bps
Bit Rate Accuracy
1%
Environmental
Operating Temperature
32°F to 122°F
(0°C to 50°C)
90% RH, non-condensing
Transient Protection
ESD
IEC 1000
EFT
IEC 1000
Surge
IEC 1000
*Level 3 is typical of an industrial environment
AC Input (as installed)
To Waveform described in ANSI/IEEE C62.41-
1991Category A Ringwave at 6Kv O.C.and Category B
Impulse at 6Kv O.C.