Installation Instructions

Document No. 550-163
Installation Instructions
June 18, 2015
Page 2 of 11 Siemens Industry, Inc.
Control Applications
6630 through 6637
Product Description
These installation instructions describe direct-
coupled mounting of the BACnet Actuating Terminal
Equipment Controller (ATEC). This is a combination
TEC and OpenAirGDE131 Non-spring Return
Rotary Electronic Damper Actuator.
A version using the GLB gear train is also available
and provides 88 in. lbs. of torque.
NOTE:
Changes to the motor setup is
required when installing the 88 in.
lb. version (550-431PA). The motor
run time must be changed to 125
seconds.
Generic Controller I/O Layout. See
Wiring Diagram
for application specific details.
Warning/Caution Notation
WARNING
CAUTION
AVERTISSMENT
ATTENTION
Risques de dommages ou de pertes
de données, si vous ne suivez pas les
procédures indiquées.
Product Numbers
Smoke Control Listed BACnet
Actuating Terminal Equipment
Controller (ATEC) (GDE)
550-430PKA
Smoke Control Listed BACnet
Actuating Terminal Equipment
Controller (ATEC) (GLB)
550-431PKA
Parts for Smoke Control Compliance
Smoke Control Listed Large Equipment
Controller Enclosure (Long board and
ATEC controllers)
550-002K
UL Listed Class 2 transformer with
120/240/277/480 Vac 50/60 HZ 0.5A
primary with hub, and 24 Vac 96VA
secondary w/ hub and circuit breaker
TR100VA004
NOTE:
For smoke control application,