Data Sheet for Product

Siemens Building Technologies, Inc. Page 3 of 4
The FLN Controller provides stand-alone DDC to
deliver precise HVAC control, and comprehensive
information about system operation. The Controller
Board processor receives information from the FLN
devices in the building, processes the information, and
through the FLN Controller devices, directly controls
the HVAC equipment. The following routines are
available in the FLN Controller:
Closed Loop Proportional, Integral and Derivative
(PID) control
Advanced loop tuning algorithm for (PID)
parameters
Logical sequencing
Alarm detection and reporting
Reset schedules
Built-in Energy Management
Routines
The following routines are programmed in the FLN
Controller and require simple parameter input for
implementation:
Peak Demand Limiting
Start-Stop Time Optimization (SSTO)
Time-of-Day and holiday scheduling
Duty cycling
Equipment optimization and sequencing
Economizer control
Specifications
Processor Type Motorola 68302
Processor Clock Speed 16.67 MHz
Memory Size
Firmware 2.X or later
6 MB - or -
8 MB
Firmware 1.X 3 MB
Battery Backup of RAM 60 days
Local Communication Interface Dual RS-232 ports
Network Communication Speed 300 bps to 115.2K bps
Voltage Requirements 115 Vac @ 60 Hz or 230 Vac @ 50/60 Hz
Enclosure Type NEMA 1
Ambient Operating Environment
+32
º
F to +120
º
F
(0
º
C to +49
º
C)
93% RH, (Non-condensing)
Agency Listings
UL 864 UUKL, (115V only)
UL 864 UDTZ, (115V only)
UL 864 QVAX, (115V only)
UL 916 PAZX,
ULC/ORD-C100-1992
UUKL7
Agency Compliance
FCC, Part 15
Class A, Subpart J
CISPR 22 Class A
Australian Compatibility Framework
Dimensions
14" W × 16" H × 4-1/2" D
(355 mm × 406 mm × 114 mm)