Application

Application 2030 Point Database
10
Siemens Industry, Inc. Application Note, App 2030 140-1021
2015-08-07
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
ANG
57 DPR2 ROT
ANG
90 -- 1 0 -- --
58 MTR SETUP 0 -- 1 0 -- --
59 DO DIR.REV 0 -- 1 0 -- --
71 FLOW P GAIN
0.25 -- 0.05 0 -- --
72 FLOW I GAIN 0.018 -- 0.001 0 -- --
73 FLOW D GAIN
0 -- 2 0 -- --
74 FLOW BIAS 50 PCT 0.4 0 -- --
{75} FLOW 0 PCT 0.25 0 -- --
{78} CTL TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
{84} DMPR
STATUS
CAL -- -- -- RECAL CAL
87 CAL MODULE
NO -- -- -- YES NO
{91} TOTAL
VOLUME
0 (0) CF (L) 4 (113) 0 -- --
{93} FLOW STPT 0 PCT 0.25 0 -- --
{94} CAL AIR NO -- -- -- YES NO
95 CAL SETUP 4 -- 1 0 -- --
96 CAL TIMER 12 HRS 1 0 -- --
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0 -- --
98 LOOP TIME 5 SEC 1 0 -- --
{99} ERROR
STATUS
0 -- 1 0 -- --
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.