Application
Table Of Contents
Sequence of Operation
Application Notes
8
Siemens Industry, Inc. Application Note, App 2030 140-1021
2015-08-07
Application Notes
If FLOW is oscillating while FLOW STPT is constant, then the flow loop requires
tuning.
The controller, as shipped from the factory, keeps all associated equipment OFF.
Spare DOs can be used as auxiliary points that are controlled by the field panel
after being defined in the field panel’s database. The combination of DO 3 and DO
4 may be used as auxiliary motor points. If using this pair of spare DOs to control a
motor, you must unbundle MTR2 COMD and set MTR SETUP.
For more information, contact your local Siemens Industry representative.
Wiring Diagrams
NOTE:
The controller’s DOs control 24 Vac loads only. The maximum rating is 12 VA for
each DO. An external interposing relay is required for any of the following:
• VA requirements higher than the maximum
• 110 or 220 Vac requirements
• DC power requirements
• Separate transformers used to power the load
(for example, part number 540-147, Terminal Equipment Controller Relay Module)
Application 2030 – Constant Volume Cooling Only.