Application

Application 2030 Point Database
9
Siemens Industry, Inc. Application Note, App 2030 140-1021
2015-08-07
Application 2030 Point Database
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
1 CTLR
ADDRESS
99 -- 1 0 -- --
2 APPLICATION
2092 -- 1 0 -- --
{04} ROOM TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
{15} AUX TEMP 74.0
(23.495556
)
DEG F
(DEG C)
0.5 (0.28) 37.5(3.055556) -- --
18 WALL
SWITCH
NO -- -- -- YES NO
{19} DI OVRD SW OFF -- -- -- ON OFF
20 OVRD TIME 0 HRS 1 0 -- --
{21}
UNOCC OVRD
UNOCC -- -- -- UNOCC OCC
{24} DI 2 OFF -- -- -- ON OFF
{25} DI 3 OFF -- -- -- ON OFF
{29} OCC.UNOCC OCC -- -- -- UNOCC OCC
{31}
UNOCC FLOW
220
(103.818)
CFM (LPS) 4 (1.8876) 0 -- --
{32} OCC FLOW 2200
(1038.18)
CFM (LPS) 4 (1.8876) 0 -- --
{35} AIR VOLUME 0 (0.0) CFM (LPS) 4 (1.8876) 0 -- --
36 FLOW COEFF
1 -- 0.01 0 -- --
40 FAIL MODE CLOSED -- -- -- CLOSED OPEN
{41} DO 1 OFF -- -- -- ON OFF
{42} DO 2 OFF -- -- -- ON OFF
{43} DO 3 OFF -- -- -- ON OFF
{44} DO 4 OFF -- -- -- ON OFF
{45} DO 5 OFF -- -- -- ON OFF
{46} DO 6 OFF -- -- -- ON OFF
{48} DMPR COMD
0 PCT 0.4 0 -- --
{49} DMPR POS 0 PCT 0.4 0 -- --
51 MTR1 TIMING
95 SEC 1 0 -- --
{52} MTR2 COMD 0 PCT 0.4 0 -- --
{53} MTR2 POS 0 PCT 0.4 0 -- --
55 MTR2 TIMING
130 SEC 1 0 -- --
56 DPR1 ROT 90 -- 1 0 -- --