Operating Instructions

Introduction
Siemens Building Technologies, Inc. 3
Hardware Outputs
Analog (0 to 10V)
Application
Cooling valve actuator
2281, 2283, 2287
Face-bypass damper actuator
2281, 2283, 2284, 2286
Heating valve actuator
2281, 2283, 2284, 2286, 2287
Outdoor air damper actuator
2281, 2283, 2284, 2286
Digital
Application
Auxiliary radiation electric coil contact; or,
auxiliary radiation two-position valve actuator
2281, 2283, 2284, 2286
Unit fan
2281, 2283, 2284, 2286, 2287
First stage electric heat
2281, 2283, 2284, 2286
Second stage electric heat
2281, 2283, 2284, 2286
Third stage electric heat
2281, 2283, 2284, 2286
Two-position cooling valve actuator
2281, 2283, 2284, 2286
Two-position heating valve actuator
2281, 2283, 2284, 2286
DX coil
2284, 2286, 2287
Power Wiring
The controller is powered by 24 Vac and connects to the two screw terminals on the
controller. Labeled “C” (Common) and “H” (Hot) on the terminal block labeled “24 VAC”. No
earth-ground connection is required (Figure 2).
Communication Wiring
The controller connects to the field panel by means of a Floor Level Network (FLN) trunk.
Communication wiring connects to the three screw terminals on the controller labeled “+”
(positive), “-“ (negative), and “S” (Shield) (Figure 3).