Operating Instructions

APOGEE Heat Pump Controller—Multi Stage Owner's Manual
28 Siemens Building Technologies, Inc.
Descriptor Address Application Description
CLG OUTPUT 61 2281, 2283,
2284, 2286,
2287
If the cooling control device is not DX, then the value of this
point indicates the position of the cooling actuator. If DX cooling
is used, then the value of this point determines whether DX is
ON or OFF.
Valid values: 0 to 100%
OA DMPR POS 62 2281, 2283,
2284, 2286,
2287
Indicates the position of the outdoor air damper actuator.
CLG P GAIN 63 2281, 2283,
2284, 2286,
2287
The proportional gain value for the cooling temperature control
loop.
CLG l GAIN 64 2281, 2283,
2284, 2286,
2287
The integral gain value for the cooling temperature control loop.
CLG D GAIN 65 2281, 2283,
2284, 2286,
2287
The derivative gain value for the cooling temperature control
loop.
CLG BIAS 66 2281, 2283,
2284, 2286,
2287
The biasing of the cooling temperature control loop. Refer to
CLG LOOPOUT (Point79).
HTG P GAIN 67 2281, 2283,
2284, 2286,
2287
The proportional gain value for the heating temperature control
loop.
HTG l GAIN 68 2281, 2283,
2284, 2286,
2287
The integral gain value for the heating temperature control loop.
HTG D GAIN 69 2281, 2283,
2284, 2286,
2287
The derivative gain value for the heating temperature control
loop.
HTG BIAS 70 2281, 2283,
2284, 2286,
2287
The biasing of the heating temperature control loop. Refer to
HTG LOOPOUT (Point 80).
ROOM P GAIN 71 2281, 2284 The proportional gain value for the room control loop.
ROOM I GAIN 72 2281, 2284 The integral gain value for the room control loop.
ROOM D GAIN 73 2281, 2284 The derivative gain value for the room control loop.
ROOM BIAS 74 2281, 2284 The biasing of the room loop output point, DISCH STPT (Point
93).
CMP MIN OFF 75 2284, 2286,
2287
The minimum time, in minutes, which the unit ventilator's
compressor will remain OFF before turning ON again.
Valid input: 0 to 255 minutes
CMP MlN ON 76 2284, 2286,
2287
The minimum time, in minutes, which the unit ventilator's
compressor will remain ON before turning OFF again.
Valid input: 0 - 255 minutes
AUX LOOPOUT 77 2281, 2284 The control loop output value that is used to determine AUX
OUTPUT (Point 55).