Data Sheet for Product
Table Of Contents
Page 2 of 5
Siemens Industry, Inc.
controller is designed for operation and modification
without vendor assistance.
If required, new custom code using our PPCL
programming language can be added to replace or
supplement the standard application residing in the
controller. This provides the flexibility to meet many
job specifications with the assurance of having a
proven and tested standard application to rely upon.
Hardware
The Siemens BACnet PTEC Heat Pump Controller
consists of an electronic controller assembly.
This controller provides all wiring terminations for
system and local communication and power. The
cable from the room sensor (purchased separately)
connects to an RJ-11 jack on the controller. All other
connections are removable terminal blocks. The
controller assembly is mounted on a plastic track that
mounts directly on the heat pump. An optional
enclosure (P/N 550-002) protects the controller
assembly.
The controller interfaces with the following external
devices:
Floating control or Spring-return damper actuator
Temperature sensors (room, mixed air)
Service and commissioning tools
Digital input devices (dry contacts from motion
sensors, alarm contacts, switches)
Digital output devices (fan, reversing valve, single
or two-stage compressor, single-stage or auxiliary
heat)
Room Sensor
The room sensor connection to the controller board
consists of a quick-connect RJ-11 jack. This
streamlines installation and reduces controller start-up
time.
Combination Temperature and Relative
Humidity Models
The Series 2200 range of TEC room units includes
combination temperature and humidity models. For
these models, both temperature and relative humidity
values are passed digitally to the TEC. This
information is passed from the room unit through the
RJ-11 cable to the RTS port on the TEC. See the
Series 2200 Temperature Room Units for TEC and
ATEC Technical Specification Sheet
(149-820), for
more information.
Heat Pump Controller
Specifications
Dimensions 4-1/8" W × 11-1/4" L × 1-1/2" H
Weight approx. 3 lbs (1.35 kg)
Controlled Temperature
Accuracy, Heating or
Cooling
±1.5°F (0.9°C)
Power Requirements
Operating Range 19.2 to 27.6 Vac, 50 or 60 Hz
Power Consumption 10 VA (plus 12 VA per DO)
Inputs
Analog 1 room temperature sensor
(10k thermistor)
1 setpoint (optional at RTS)
2 auxiliary temperature sensor
(10k thermistor)
1 selectable 0-10 Vdc/4-20 mA
Digital 2 dry contacts (plus 1 override
switch, optional, part of RTS)
Outputs
Analog 3 0-10 Vdc
Digital 8 DO 24 Vac optically isolated
solid state switches @ 0.5 amp
Communications
Remote BACnet MS/TP (EIA 485), 9600
bps to 76800 bps FLN Trunk
Local WCIS and PTEC Tool
Ambient Conditions
Shipping & Storage
Temperature
-13°F to 158°F (-25°C to 70°C)
Operating Temperature 32°F to 122°F (0°C to 50°C)
Humidity Range 5% to 95% rh (non-condensing)