Product Description
For TEC applications using a SSC81.5U actuator
requiring fail-safe (spring return) action and floating
(three-point) control.
Product Number
550-500
Contents
Two 1.5K-ohm resistors (1-watt, 5% accuracy).
Resistor color bands: Brown/Green/Red/Gold
Required Tools
Small flat-blade screwdriver
Expected Installation Time
10 minutes
Installation
Install the resistors from both DO Terminals to the
common terminal. See Figure 1.
The installation is now complete.
Figure 1. 1.5K-Ohm Wiring Diagram.