Installation Instructions

Installation Instructions
Document No. 129-539
November 5, 2008
TEC Digital Flush Mount Sensor Wall
Mounting Kit
Item Number 129-539, Rev. AA Page 1 of 2
Product Description
This kit allows users to mount the TEC Semi-Flush
Mount Room Temperature Sensor on standard drywall
or to a 2" × 4" electrical box. It can also be used on
plywood, paneling, or other types of wall sheathing
material.
Contents
Backplate (1)
6-32 × 1-7/8" Screw (2)
#6-8 × 3/4" Plastic wall anchor (2)
Product Number
AQA1200
Required Tools
Pencil or marker
Small level
3/16” drill bit
Med. duty electric or battery operated hand drill
Phillips head screw driver
Drywall saw
Linesman pliers
Expected Installation Time
15 minutes
Prerequisites
Review these instructions before beginning.
Installed: Appropriate field wiring (standard six-
conductor room sensor cables, plenum or non-
plenum as required), within the maximum
wiring run length for the individual equipment
controller. The maximum recommended length
is 100 feet (30 m).
All wring must comply with the National Electric
Code (NEC) and local regulations.
Locate the sensor:
According to design specifications and local
regulations.
Where the air circulates around it freely (not in
recessed areas or behind doors).
Away from drafts caused by doors, windows,
outside walls, air registers, pipes, and return air
plenums, and so on.
On an inside wall (preferably), about 5 feet
(1.5 m) above the finished floor.
Installation
A typical installation procedure consists of the following
steps:
Drywall Mounting
1. Place the backplate in the up position "" level
on the wall and trace inside to make roughly a
2-1/16" × 3-1/2" rectangle. See Figure 1.
Figure 1. Drywall Mounting.
2. Choose two holes and mark their centers.
3. Drill two 3/16" holes where the hole centers are
marked.

Summary of content (2 pages)