Application

Application 2032 Point Database
13
Siemens Industry, Inc. Application Note, App 2032 140-1022
2015-08-07
Application 2032 Point Database
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
1 CTLR
ADDRESS
99 -- 1 0 -- --
2 APPLICATION
2092 -- 1 0 -- --
{04} ROOM TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
{05} HEAT.COOL COOL -- -- -- HEAT COOL
6 OCC CLG
STPT
70.0
(21.20888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
7 OCC HTG
STPT
70.0
(21.20888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
8 UOC CLG
STPT
65.0
(18.40888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
9 UOC HTG
STPT
65.0
(18.40888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
11 RM STPT MIN
55.0
(12.80888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
12
RM STPT MAX
90.0
(32.40888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
{13} RM STPT
DIAL
74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
14 STPT DIAL NO -- -- -- YES NO
{15} AUX TEMP 74.0
(23.495556
)
DEG F
(DEG C)
0.5 (0.28) 37.5(3.055556) -- --
18 WALL
SWITCH
NO -- -- -- YES NO
{19} DI OVRD SW OFF -- -- -- ON OFF
20 OVRD TIME 0 HRS 1 0 -- --
{21}
UNOCC OVRD
UNOCC -- -- -- UNOCC OCC
{24} DI 2 OFF -- -- -- ON OFF
{25} DI 3 OFF -- -- -- ON OFF
{29} OCC.UNOCC OCC -- -- -- UNOCC OCC
{31}
UNOCC FLOW
220
(103.818)
CFM (LPS) 4 (1.8876) 0 -- --
{32} OCC FLOW 2200
(1038.18)
CFM (LPS) 4 (1.8876) 0 -- --
{35} AIR VOLUME 0 (0.0) CFM (LPS) 4 (1.8876) 0 -- --
36 FLOW COEFF
1 -- 0.01 0 -- --
40 FAIL MODE CLOSED -- -- -- CLOSED OPEN