Application

Application 2032 Point Database
15
Siemens Industry, Inc. Application Note, App 2032 140-1022
2015-08-07
Point
Number
Descriptor
Factory
Default (SI
Units)
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
89 STAGE TIME 10 MIN 1 0 -- --
{91} TOTAL
VOLUME
0 (0) CF (L) 4 (113) 0 -- --
{92} CTL STPT 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14)
48.0(8.88888) -- --
{93} FLOW STPT 0 PCT 0.25 0 -- --
{94} CAL AIR NO -- -- -- YES NO
95 CAL SETUP 4 -- 1 0 -- --
96 CAL TIMER 12 HRS 1 0 -- --
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0 -- --
98 LOOP TIME 5 SEC 1 0 -- --
{99} ERROR
STATUS
0 -- 1 0 -- --
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)