Application
Table Of Contents
Sequence of Operation
Control Temperature Setpoints
7
Siemens Industry, Inc. Application Note, App 2033 140-1023
2015-08-07
The setpoint deadband exists to allow the controller to provide a separation of the
heating and cooling temperature setpoints when a setpoint dial is enabled.
The setpoint deadband is the difference between the cooling and heating day setpoints
(DAY CLG STPT - DAY HTG STPT). The setpoint deadband can be disabled by
setting DAY HTG STPT equal to DAY CLG STPT. When DAY HTG STPT does not
equal DAY CLG STPT, a setpoint deadband (or zero energy band) is used.
The following values are used in the calculation of CTL STPT:
Dial value
is the value of RM STPT DIAL limited between the value of RM STPT
MIN and RM STPT MAX.
Deadband
is the value of the difference between DAY CLG STPT and DAY HTG
STPT, half of which is applied to establish the current heating and cooling
setpoints.
–
Deadband
= (DAY CLG STPT – DAY HTG STPT)
CTL STPT is calculated as follows:
With Deadband disabled:
CTL STPT =
Dial value
With Deadband enabled in Heat Mode:
CTL STPT =
Dial value
– 0.5 ∗
Deadband
(limited between the value of RM STPT MIN
and RM STPT MAX)
With Deadband enabled in Cool Mode:
CTL STPT =
Dial value
+ 0.5 ∗
Deadband
(limited between the value of RM STPT MIN
and RM STPT MAX)
NOTE:
If RM STPT DIAL is failed, it maintains the last known value.