DXR Actuator Package DXR2.M12P and GDE131.1U The DXR Actuator Package pairs a terminal equipment controller (DXR) with a GDE131.1U Actuator on a common plate. It is a low cost solution for field applications requiring VAV or CV applications with an electronic actuator. ● ● ● A6V10549990 27.10.2015 Pre-assembled package. Reduced installation time. Reduced cost. Siemens Industry, Inc.
Features The DXR/Actuator Package reduces installation time, and therefore cost, by providing the Field Installer a pre-assembled package that mounts in less time than what is required to separately mount the components. Technical Design Components ● DXR Controller (DXR2.M12P) ● GDE Actuator (GDE131.1U) ● Mounting plate (550-009A) Type summary Product Description DXR2.M12P-102B-GDE DXR Actuator DXR2.M12P* GDE131.
Actuator Technical Data Power supply Power supply Operating voltage 24 Vac +15%, -15% Frequency 50/60 Hz. Power consumption including connected field devices 2.3 VA Functional data AC 24 V supply for field devices Output power Max. 4 VA total Protection against overload Power limitation internal, max. 250 mA, resetting. Environmental compatibility Function Torque 44 lb-in (5 Nm) Runtime for 90° opening or closing 90 sec. At 60 Hz (108 sec.
DXR2 Technical data Dimensions 259 (10.2) x 168 (6.6) x 93 (3.7) Weight 1.0 kg (2.1 lbs) Power data Power supply Operating voltage AC 24 V -15%/+20% Frequency 50/60 Hz Internal fuse 4 A irreversible Transformer with secondary current limitation of max. 10 A or external secondary current fuse Non-renewable fuse Circuit breakers Apparent power (VA) for transformer design Base load including I/O without load by field devices DXR2.M12P.. 6 Max. output Max.
Outputs Analog Outputs 0 to 10 V 1.5 mA maximum Digital Outputs Type (Switching outputs triacs) High side The Triac closes the contact to AC 24 V Switching voltage AC 24 V Permissible load 250 mA / 6 VA per output Protection Short-circuit proof AC 24V outputs for field devices (2: V~) Building Technologies Output voltage AC 24 V Permissible load 500 mA/12 VA overall Protection against overload Short-circuit proof 5 A6V10549990 27.10.
Conformity CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage ● Observe national provisions and comply with the appropriate safety regulations. Ambient conditions and protection classification Climatic ambient conditions ● Transport and Storage ● ● Operation ● Temperature -25...70 °C (-13... 158°F) Air humidity 5...95% rh. Temperature -5...50 °C (23... 122 F) Air humidity 5...95% rh.