Data Sheet for Product

4
Building Technologies
A6V10549990
27.10.2015
Dimensions
259 (10.2) x 168 (6.6) x 93 (3.7)
Weight
1.0 kg (2.1 lbs)
Power data
Power supply
Operating voltage
AC 24 V -15%/+20%
Frequency
50/60 Hz
Internal fuse 4 A irreversible
Transformer with secondary current limitation of
max. 10 A or external secondary current fuse
Non-renewable fuse
Circuit breakers
Apparent power (VA) for transformer design
Base load
including I/O
without load
by field
devices
Max. output
load Triac at
250 mA each
Max. load for
AC 24 V field
supply at
250 mA
Max. load
KNX PL-Link
at 50 mA
Max. load for
DC 24 V field
supply at 100
mA
Power
consumption
including
connected
field devices
DXR2.M12P..
6
6 x 6 = 36
(72 with
PWM *)
12
4
-
58
(94 with
PWM *)
Inputs
Analog Inputs
Resistance sensor
Temperature measurement
Voltage measurement
AI 1000 Ω
AI PT1K 375
AI 0 to 10 V
AI 2500 Ω
AI PT1K 385
AI 0 to 10 V (0 to 100%)
AI 10 KΩ
AI Ni1000*
AI 100 KΩ
AI Ni1000 DIN
AI NTC3K
AI NTC10K*
AI NTC100K*
*)
Configurable default.
Digital Inputs
Contact voltage
DC 17 V typical
Contact current
1.5 mA typical, 7 mA initial current
Contact resistance for closed contacts
Less than 100
Contact resistance for open contacts
Greater than 50 KΩ
Differential pressure sensor
Connections (nipple diameter)
Dia. 5.2 mm (0.20 in)
Measuring range
0 to 500 Pa (0 - 2.01 in WC)
Overload range
0 to 100 kPa (0 - 402 in WC)