Operating Instructions
Table Of Contents
Chapter 3 – Point Database
15
Siemens Industry, Inc. Owner's Manual 125-5070
2015-05-07
Descriptor
Address
1
Application
Description
DO 4 {44} All
except
2092 Digital output 4 controls a 24 Vac load with an ON or OFF
status. If Motor 2 is enabled, then DO 4 is coupled with DO 3
to control an actuator.
HEAT STAGE 2 {44} 2032 This point is DO 4 in applications with electric reheat. This
output controls the contactor for the second heating stage
and has a status of ON or OFF.
DO 5 {45} All
except
2030 Digital output 5 controls a 24 Vac load with an ON or OFF
status. If Motor 3 is used, this point is coupled with DO 6
(Application 2092 only).
HEAT STAGE 3 {45} 2032 This point is DO 5 in applications with electric reheat. This
output controls the contactor for the third heating stage and
has a status of ON or OFF.
DO 6 {46} All Digital output 6 controls a 24 Vac load with an ON or OFF
status. If Motor 3 is used, this point is coupled with DO 5..
DMPR COMD {48} All
except
2092 The value to which the cold duct damper motor is
commanded in percent of full travel.
MTR1 COMD {48} 2092 The value to which the Motor 1 actuator is commanded in
percent of full travel.
DMPR POS {49} All
except
2092 The current position of the damper motor in percent of full
travel. This value is calculated based on motor run time.
MTR1 POS {49} 2092 The current position of Motor 1 in percent of full travel. This
value is calculated based on motor run time. See
MTR1
TIMING
.
MTR1 TIMING 51 All The time, in seconds, required for the Motor 1 actuator to
travel from full closed to the full open position.
MTR2 COMD {52} 2092 The value to which the Motor 2 actuator is commanded in
percent of full travel (for use as an auxiliary slave point).
VLV COMD {52} 2033 The value to which the valve actuator is commanded in
percent of full travel for applications using a water valve..
MTR2 POS {53} 2030, 2092 The current position of the Motor 2 actuator in percent of full
travel (for use as an auxiliary slave point). This value is
calculated based on motor run time. See
MTR2 TIMING
.
VLV POS {53} 2033 The current position of the valve in percent of full travel for
applications using a water valve. This value is calculated
based on motor run time.
MTR2 TIMING 55 All
except
2092 The time, in seconds, required for the Motor 2 actuator to
travel from full closed to the full open position.
DPR1 ROT ANG 56 All The number of degrees that damper 1 is free to travel.
DPR2 ROT ANG 57 2030, 2092 The number of degrees that damper 2, the hot duct damper,
is free to travel.
MTR SETUP 58 All The configuration setup code for Motors 1 and 2. This
enables the motors individually and sets each motor to be
either direct or reverse acting.
Note:
When a motor is enabled, its associated DOs are
enabled.
DO DIR.REV 59 All The configuration setup code for DOs. Allows the DOs to be
direct or reverse acting (enabled equals energized or
disabled equals de-energized).
EHEAT FLOW 60 2032 Area, in square feet (square meters), of duct 2 where the air