Application

Application 2486 Point Database
6
Siemens Industry, Inc. Application Note, App 2486 140-1226
2015-05-07
Application 2486 Point Database
Point
Number
Descriptor
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
1 CTLR ADDRESS 99 -- 1 0 -- --
2 APPLICATION 2486 -- 1 0 -- --
{03} CHK STATUS -1 -- 1 -1 -- --
{04} ROOM TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
{10} CHK OUT NO -- -- -- YES NO
{13} RM STPT DIAL 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
{19} DI OVRD SW OFF -- -- -- ON OFF
{29} DAY.NGT DAY -- -- -- NIGHT DAY
{35} AIR VOLUME 0 (0.0) CFM (LPS) 4 (1.8876) 0 -- --
36 FLOW COEFF 1 -- 0.01 0 -- --
{41} DO 1 OFF -- -- -- ON OFF
{42} DO 2 OFF -- -- -- ON OFF
{48} MTR1 COMD 0 PCT 0.4 0 -- --
{49} MTR1 POS 0 PCT 0.4 0 -- --
51 MTR1 TIMING 95 SEC 1 0 -- --
56 DPR1 ROT ANG 90 -- 1 0 -- --
58 MTR SETUP 0 -- 1 0 -- --
59 DO DIR. REV 0 -- 1 0 -- --
{94} CAL AIR NO -- -- -- YES NO
95 CAL SETUP 4 -- 1 0 -- --
96 CAL TIMER 12 HRS 1 0 -- --
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0 -- --
{99} ERROR STATUS 0 -- 1 0 -- --
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.