Data Sheet for Product
Table Of Contents
- Room Pressurization Controllers
- Features
- Applications
- Hardware
- Differential Pressure Transducer
- Autozero Module
- Pneumatic Output Module
- Room Pressurization Controller – Electronic Output Specifications
- Room Pressurization Controller – Pneumatic Output Specifications
- Pressure Mode Switch
- Communication
- Product Ordering Information
- Document Information
Siemens Industry, Inc.
Page 3 of 5
Pneumatic Output Module Specifications
Maximum Input Pressure
30 psi
Air Consumption
4 SCIM (1.1 ml/sec)
Power Consumption
1.5 VA @ 24 Vac max.
Dimensions 2-1/2" W x 4-1/2" H x 1-1/4" D
(64 mm x 114 mm x 32 mm)
Weight
0.5 lbs (0.2 kg)
Room Pressurization Controller –
Electronic Output Specifications
Power Requirements
Operating Range
Power Consumption
19 to 28, Vac 50 Hz or 60 Hz
3.8 VA (Nominal) to
5.3 VA (Peak) @ 24 Vac
(plus loads)
Inputs
Analog
Digital
1 room temperature sensor
2 velocity sensors
(Optional) 1 setpoint
1 auxiliary temperature sensor
or
1 pressure mode switch
3 dry contacts
Outputs 8 DO 24 Vac optically isolated
solid state switches @ 0.5 amp
Dimensions 4-1/8" W x 11-1/4" L x 2" H
(105 mm x 286 mm x 51 mm)
Weight
approx. 3 lbs (1.35 kg)
Controlled Temperature
Accuracy, Heating or
Cooling
±1.5°F (0.9°C)
Ambient Conditions
Storage Temperature
Operating
Temperature
Humidity Range
-40°F to 167°F (-29°C to 75°C)
32°F to 122°F (0°C to 50°C)
10% to 95% (non-condensing)
Agency Listings
UL Listing
cUL Listed
UL Smoke Control
FCC Compliance
UL 916, PAZX
Canadian Standards C22.2 No.
205-M1983, PAZX7
UL 864, PAZX, UDTZ
47 CFR Part 15, Class A
Communications
Remote
Local
9600 bps to 76800 LAN Trunk
WCIS
Room Pressurization Controller –
Pneumatic Output Specifications
Power Requirements
Operating Range
Power Consumption
19 to 28 Vac, 50 or 60 Hz
11.5 VA (Nominal) to
20 VA (Peak) @ 24 Vac
Inputs
Analog
Digital
1 room temperature sensor
2 velocity sensors
(Optional) 1 setpoint
1 auxiliary temperature sensor
or
1 pressure mode switch
3 dry contacts
Outputs
Analog
Digital
3 pneumatic output
1 DO 24 Vac optically isolated
solid state switch @ 0.5 amp
Dimensions
12" W x 12" L x 4" D
(306 mm x 306 mm x 102 mm)
Weight
approx. 8 lbs (3.6 kg)
Controlled Temperature
Accuracy, Heating or
Cooling
±1.5°F (0.9°C)
Ambient Conditions
Storage Temperature
Operating
Temperature
Humidity Range
-40°F to 167°F (-29°C to 75°C)
32°F to 122°F (0°C to 50
°
C)
5% to 95% rh (non-condensing)
Agency Listings
UL Listing
cUL Listed
UL Smoke Control
FCC Compliance
UL 916, PAZX
Canadian Standards C22.2 No.
205-M1983, PAZX7
UL 864, PAZX, UDTZ
47 CFR Part 15, Class A
Communications
Remote
Local
9600 bps to 76800 LAN Trunk
WCIS
Pressure Mode Switch
The Room Pressurization Controller Pressure Mode
Switch changes the pressurization of the room from
protective isolation (positive), to infectious isolation
(negative), to no isolation. This keyed switch also
includes a light to indicate when the controller cannot
maintain the programmed differential flow in the room.
The stainless steel flush mounted switch can be
mounted outside a patient/treatment room or at a
nurse’s station.