Data Sheet for Product

Page 4 of 5
Siemens Industry Inc.
Pressure Mode Switch Specifications
Power Consumption
1.1 VA @ 24 Vac max.
Dimensions 4" H x 4.5" W
(102 mm x 114 mm)
Weight
1 lb (0.4 kg)
Communication
Up to 32 Room Pressurization Controllers or other
Terminal Equipment Controllers (TEC) can be
connected to each of the three Protocol 2 field panel
LAN trunks, for a total of 96 per field panel.
Communication with the controller can be initiated from
any Siemens field panel on the network. The network
does not require additional hardware to connect TECs.
When TECs are wired to a field panel, features such
as energy management programs, alarm reporting,
centralized control, modification of the system
database, system-wide troubleshooting, and the global
commanding of devices are available to them.