Data Sheet for Product
Siemens Industry, Inc.
Page 3 of 6
Transient Protection
ESD IEC 1000-4-2 level 3*
EFT IEC 1000-4-4 level 3*
Surge IEC 1000-4-5 level 3*
*Level 3 is typical of an industrial environment
AC Input 115V/230V Transient protection (as installed with required
minimum of 3 MOVs (H-N), (H-E), and (N-E) rated 40 joules
each).
Protection to waveform described in ANSI/IEEE C62.41-1996
Category B ringwave @ 6 kV O.C. and Category B impulse @ 6
kV O.C.
APOGEE ALN/FLN Max
Voltage
5 Vdc
Operating Voltage 6 Vdc, via 115/230 Vac
Power Pack @ 14W
Diagnostic LEDs 1 LED per fiber Receive Data port
1 LED per fiber Transmit Data port
1 LED to indicate presence of DC power
Agency Listings
UL Smoke Control Equipment (UUKL)
Energy Management Equipment (PAZX)
ULC/ORD-C100-1992 Smoke Control Equipment (UUKL7)