Application

Application 2520 Point Database
12
Siemens Industry, Inc. Application Note, App 2520 140-1217
2015-05-06
Application 2520 Point Database
Point
Number
Descriptor
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
1 CTLR ADDRESS 99 -- 1 0 -- --
2 APPLICATION 2486 -- 1 0 -- --
{03} CHK STATUS -1 -- 1 -1 -- --
{04} ROOM TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
6 DAY CLG STPT 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
8 NGT CLG STPT 82.0
(27.92888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
{10} CHK OUT NO -- -- -- YES NO
11 RM STPT MIN 55.0
(12.80888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
12 RM STPT MAX 90.0
(32.40888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
{13} RM STPT DIAL 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
14 STPT DIAL NO -- -- -- YES NO
{19} DI OVRD SW OFF -- -- -- ON OFF
20 OVRD TIME 0 HRS 1 0 -- --
{21} NGT OVRD NIGHT -- -- -- NIGHT DAY
{29} DAY.NGT DAY -- -- -- NIGHT DAY
31 CLG FLOW MIN 220
(103.818)
CFM (LPS) 4 (1.8876) 0 -- --
32 CLG FLOW MAX 2200
(1038.18)
CFM (LPS) 4 (1.8876) 0 -- --
{35} AIR VOLUME 0 (0.0) CFM (LPS) 4 (1.8876) 0 -- --
36 FLOW COEFF 1 -- 0.01 0 -- --
{41} DO 1 OFF -- -- -- ON OFF
{42} DO 2 OFF -- -- -- ON OFF
{48} DMPR COMD 0 PCT 0.4 0 -- --
{49} DMPR POS 0 PCT 0.4 0 -- --
51 MTR1 TIMING 95 SEC 1 0 -- --
56 DMPR ROT ANG 90 -- 1 0 -- --
58 MTR SETUP 0 -- 1 0 -- --
59 DO DIR. REV 0 -- 1 0 -- --
63 CLG P GAIN 20.0 (36.0) -- 0.25 (0.45) 0 -- --