Application

Application 2520 Point Database
13
Siemens Industry, Inc. Application Note, App 2520 140-1217
2015-05-06
Point
Number
Descriptor
Factory
Default
(SI Units)
2
Eng Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
64 CLG I GAIN 0.01 (0.018) -- 0.001
(0.0018)
0 -- --
65 CLG D GAIN 0 (0.0) -- 2 (3.6) 0 -- --
66 CLG BIAS 0 PCT 0.4 0 -- --
71 FLOW P GAIN 0 -- 0.05 0 -- --
72 FLOW I GAIN 0.01 -- 0.001 0 -- --
73 FLOW D GAIN 0 -- 2 0 -- --
74 FLOW BIAS 50 PCT 0.4 0 -- --
{75} FLOW 0 PCT 0.25 0 -- --
{76} CTL FLOW MIN 220
(103.818)
CFM (LPS) 4 (1.8876) 0 -- --
{77} CTL FLOW MAX 2200
(1038.18)
CFM (LPS) 4 (1.8876) 0 -- --
{78} CTL TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
{79} CLG LOOPOUT 0 PCT 0.4 0 -- --
{92} CTL STPT 74.0
(23.44888)
DEG F
(DEG C)
0.25 (0.14) 48.0
(8.88888)
-- --
{93} FLOW STPT 0 PCT 0.25 0 -- --
{94} CAL AIR NO -- -- -- YES NO
95 CAL SETUP 4 -- 1 0 -- --
96 CAL TIMER 12 HRS 1 0 -- --
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0 -- --
98 LOOP TIME 5 SEC 1 0 -- --
{99} ERROR STATUS 0 -- 1 0 -- --
1)
Points not listed are not used in this application.
2)
A single value in a column means that the value is the same in English units and in SI units.
3)