Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power to the Controller
- Enabling Actuators
- Setting the Application
- Setting Number of Heat Stages or Valves
- Enabling Autozero Module
- Selecting Automatic Calibration Option
- Setting Room Temperature Setpoints
- Setting Override Time
- Enabling Wall Switch
- Setting Fail Mode
- Setting Duct Area
- Setting Flow Coefficient
- Setting Airflow Setpoints
- Setting Controller Address
- Secure Mode
Before You Begin
Secure Mode
12
Siemens Industry, Inc. Start-up Procedures 140-1020
2015-05-07
Secure Mode
After updating the controller at the field panel, Secure Mode can be enabled/disabled
through the Insight workstation.
Once enabled, modification of any configuration or override points is prevented. See
application documentation for more information.