Commissioning Instructions
Table Of Contents
- Before You Begin
- Verifying Power to the Controller
- Enabling Actuators
- Setting the Application
- Setting Number of Heat Stages or Valves
- Enabling Autozero Module
- Selecting Automatic Calibration Option
- Setting Room Temperature Setpoints
- Setting Override Time
- Enabling Wall Switch
- Setting Fail Mode
- Setting Duct Area
- Setting Flow Coefficient
- Setting Airflow Setpoints
- Setting Controller Address
- Secure Mode
Before You Begin
Enabling Actuators
6
Siemens Industry, Inc. Start-up Procedures 140-1020
2015-05-07
NOTE:
The assumptions for this table are:
- Dampers are Normally Closed (NC)
- Heating valves are Normally Open (NO)
MTR SETUP Value for Most Common Configurations.
Applications
Configurations
Value for
MTR SETUP
Motor 1
Motor 2
2030 Damper (normally
closed)
Not used 1
2032 Damper (normally
closed)
Not available 1
2033 Damper (normally
closed)
Heating valve
(normally open)
13
Non-Standard Configuration
If your application does not use one of the listed actuators or if one of your actuators
has a different normal position than what is listed in the Table
MTR SETUP Value for
Most Common Configurations
, or if you want to use a spare motor, use the Table
Motor Enable/Reverse Values for MTR SETUP
to set MTR SETUP.
Motor Enable/Reverse Values for MTR SETUP.
Motor 1 Not Used
Motor 1 Enabled
Motor 1 Enabled
and Reversed
Motor 2 Not Used
0 1 3
Motor 2 Enabled
4 5 7
Motor 2 Enabled and Reversed
12 13 15
Verifying Actuator Setup
1. Command all actuators closed. Verify that they close and remain closed. If not,
adjust the setting for MTR SETUP according to Table
MTR SETUP Value for Most
Common Configurations
.
2. If any of the actuators still do not close completely, then the actuators have been
installed or set up incorrectly. See the TEC Constant Volume Controller Installation
Instructions (540-1020), the iKnow Troubleshooting Tool, or contact Technical
Support.