Commissioning KNX
When only one device is connected to the KNX PL-Link bus, the operating display panel
automatically establishes communications with the Fume hood controller, from where the
functions are downloaded to the operating display panel (plug & play).
Addressing:
1. Short press the programming pin (<0.5 sec).
The device goes into programming mode; the service LED is continuously on.
The tool identifies the current operating display panel that is operated and assigns it.
2. After the device is commissioned, deactivate the programming mode by shortly pressing the
programming pin (<0.5 s). The service LED goes off.
Note: Programming mode resets to “disabled” each time the device restarts.
Factory reset:
1. Long press the programming pin (>20 s). The device is locked and reboots within 10
seconds. The Fume hood controler deletes it from its device list. During this time, it is safe to
remove the device from the network.
If the bus plug remains connected, the device acts like a newly inserted device requiring
again automated or manual configuration.
Note: This operation resets all user preference data and configuration settings to factory default.
This operation is irreversible.
Disposal
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations". Siemens rejects any and all warranties in the event that third-
party products are used.