Installation Instructions
Document Number 550-308
Installation Instructions
Rev. 1, July, 2001
Siemens Building Technologies, Inc. Page 7 of 9
CAUTION:
The controller’s DOs control 24 Vac loads only. The maximum rating is 12 VA for each DO.
Use an interposing 220V 4-relay module for any of the following:
• VA requirements higher than maximum
• 110 or 220 Vac
• DC power
• Separate transformers used to power the load.
NOTE: Refer to the unit wiring diagrams or consult with the local representative if terminations are
missing or are different.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ROOM TEMPERATURE SENSOR
PRESSURE MODE SWITCH (OPTIONAL); OR,
SPARE AI (100K THERMISTOR ONLY); OR,
SPARE DI (DRY CONTACT CLOSURE ONLY)
WALL SWITCH (OPTIONAL); OR,
SPARE DI (DRY CONTACT CLOSURE ONLY)
AVS 1 AUTOZERO MODULE OR ELECTRIC HEAT
STAGE 3 (OPTIONAL); OR, SPARE DO
TECCE-2237-2268EHWDR1
24 V-AC
BST
RX
FLN TRUNK
+ - S
TX
RTS
DO 1
NO C
DO 2
NO C
DO 3
NO C
DO 4
NO C
DO 5
NO C
DO 6
NO C
DI 3
AI 3
DI 2
DO 7
NO C
DO 8
NO C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
C H GND
+-S
EHC
Y1 G Y2
CW
COMMON
CCW
COLD DUCT
DAMPER
ACTUATOR
Y1 G Y2
CW
COMMON
CCW
HOT DUCT
DAMPER
ACTUATOR
ELECTRIC HEAT STAGE 2 (OPTIONAL); OR, SPARE DO
ELECTRIC HEAT STAGE 1 (OPTIONAL); OR, SPARE DO
AVS 2 AUTOZERO MODULE (OPTIONAL); OR,
SPARE DO
Figure 7. Point Wiring for Applications 2237, 2238, 2267, and 2268 with Electric Reheat.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
ROOM TEMPERATURE SENSOR
WALL SWITCH (OPTIONAL); OR,
SPARE DI (DRY CONTACT CLOSURE ONLY)
AVS 1 AUTOZERO MODULE (OPTIONAL); OR,
SPARE DO
TECCE-2237-2268HWHWDR1
24 V-AC
BST
RX
FLN TRUNK
+ - S
TX
RTS
DO 1
NO C
DO 2
NO C
DO 3
NO C
DO 4
NO C
DO 5
NO C
DO 6
NO C
DI 3
AI 3
DI 2
DO 7
NO C
DO 8
NO C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
C H GND
+-S
EHC
Y1 G Y2
CW
COMMON
CCW
COLD DUCT
DAMPER
ACTUATOR
Y1 G Y2
CW
COMMON
CCW
HOT DUCT
DAMPER
ACTUATOR
VALVE ACTUATOR
(OR SPARE DOs)
O
P
E
N
CC
L
O
S
E
D
AVS 2 AUTOZERO MODULE (OPTIONAL); OR,
SPARE DO
SPARE AI (100K THERMISTOR ONLY); OR,
SPARE DI (DRY CONTACT CLOSURE ONLY)
Figure 8. Point Wiring for Applications 2237, 2238, 2267, and 2268 with Hot Water Reheat.