Operating Instructions

Chapter 3—Applications for ATEC—VAV with Reheat
3-62 Siemens Building Technologies, Inc.
Wiring Diagram
Figure 3-19 shows the point wiring for Application 2524.
CAUTION:
The controller’s DOs control 24 Vac loads only. The maximum rating is 12 VA for
each DO. Use an interposing relay for any of the following:
VA requirements higher than the maximum
110 or 220 Vac requirements
DC power requirements
Separate transformers used to power the load
Lo
H
i
24 Vac
FLN
RTS
90
90
4
5
TEC2524WDR1
654321
Electric Heat Stage 1
Fan
Spare AI (100K Thermistor) or
Spare DI (Dry contact closure only)
Wall Switch or
Spare AI (100K Thermistor) or
Spare DI (Dry contact closure only)
BST/FLN LED
Figure 3-19. Application 2524 Wiring Diagram.