Application 2524: VAV Series Fan Powered with One Stage of Electric Reheat
Siemens Building Technologies, Inc. 3-65
Table 3-10. Point Database for Application 2524
Point
Number
Descriptor Factory
Default
(SI Units)
Eng.
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
64 CLG I GAIN 0.01
(0.018)
– 0.001
(0.0018)
0.0 –
65 CLG D GAIN 0 (0.0) 2 (3.6) 0
66 CLG BIAS 0.0 PCT 0.4 0.0
67 HTG P GAIN 10.0 (18.0) 0.25 (0.45) 0.0
68 HTG I GAIN 0.01
(0.018)
– 0.001
(0.0018)
0.0 –
69 HTG D GAIN 0 (0.0) 2 (3.6) 0
70 HTG BIAS 0.0 PCT 0.4 0.0 – –
71 FLOW P GAIN 0.0 0.05 0.0
72 FLOW I GAIN 0.01 0.001 0.0
73 FLOW D GAIN 0 2 0
74 FLOW BIAS 50.0 PCT 0.4 0.0
{75} FLOW 0.0 PCT 0.25 0.0
{76} CTL FLOW MIN 220
(103.818)
CFM (LPS) 4 (1.8876) 0
{77} CTL FLOW MAX 2200
(1038.18)
CFM
(LPS)
4
(1.8876)
0 –
{78} CTL TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25
(0.14)
48.0
(8.88888)
– –
{79} CLG LOOPOUT 0.0 PCT 0.4 0.0
{80} HTG LOOPOUT 0.0 PCT 0.4 0.0
{81} AVG HEAT OUT 0.0 PCT 0.4 0.0
82 STAGE MAX 90.0 PCT 0.4 0.0
83 STAGE MIN 10.0 PCT 0.4 0.0
85 SWITCH LIMIT 5.2 PCT 0.4 0.0
86 SWITCH TIME 10 MIN 1 0
88 STAGE COUNT 1 1 0
89 STAGE TIME 10 MIN 1 0
90 SWITCH DBAND 1.0
(0.56)
DEG F
(DEG C)
0.25
(0.14)
0.0 –
1. Points not listed are not used in this application
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets {} may be unbundled at the field panel.
Continued on next page…