Application 2473: Slave Mode
Siemens Building Technologies, Inc. 3-83
Table 3-14. Point Database for Application 2473.
Point
Number
Descriptor Factory Default
(SI Units)
Eng. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
{43} DO 3 OFF – – – ON OFF
{44} DO 4 OFF – – – ON OFF
{48} MTR1 COMD 0.0 PCT 0.4 0.0 – –
{49} MTR1 POS 0.0 PCT 0.4 0.0 – –
51 MTR1 TIMING 95 SEC 1 0 – –
{52} MTR2 COMD 0.0 PCT 0.4 0.0 – –
{53} MTR2 POS 0.0 PCT 0.4 0.0 – –
55 MTR2 TIMING 130 SEC 1 0 – –
56 DPR1 ROT ANG 90 – 1 0 – –
57 DPR2 ROT ANG 90 – 1 0 – –
58 MTR SETUP 1 – 1 0 – –
59 DO DIR. REV 0 – 1 0 – –
87 CAL MODULE NO – – – YES NO
{94} CAL AIR NO – – – YES NO
95 CAL SETUP 4 – 1 0 – –
96 CAL TIMER 12 HRS 1 0 – –
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0.0 – –
{99} ERROR STATUS 0 – 1 0 – –
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.