Operating Instructions

Chapter 5—Troubleshooting
5-22 Siemens Building Technologies, Inc.
Equipment Checks
FLN Trunk Connections Check
If the controller connects to a field panel via a Floor Level Network (FLN), make sure that the
wiring is terminated properly at both the field panel and at the controller's FLN trunk terminal
blocks. The wires should not be shorted or loosely connected. Maintain proper FLN trunk polarity:
+ to +; to . Verify that the shields are properly terminated. See Figure 5-7.
If the FLN Trunk wiring is reversed, then the controller's BST/FLN LED will remain illuminated
steadily.
It is normal for the BST/FLN LED to be illuminated steadily if there is no FLN trunk connected to
the controller.
TEC0463R1
+
-
S
(SHIELD) (SHIELD)
(+)
(+)
(-)
(-)
Figure 5-7. FLN Trunk Wiring.
DI 3 and DI 4 Check
To check if DI 3 and DI 4 are functioning properly, use the following procedure.
Equipment Required
Jumper wire (use a 3-inch (76-mm) piece of wire, stripped at both ends, or equivalent).
Datamate (Base or Advanced) and IBM-compatible computer, or Handheld PC or Pocket
PC™ with Windows CE, plus communications cable.
Procedure
1. Plug into the communication port on the room temperature sensor. Scroll so that the
display shows DI 4 (Point 24) or DI 3 (Point 25).