Operating Instructions

Chapter 5—Troubleshooting
5-26 Siemens Building Technologies, Inc.
Clearing an Error Condition
To clear an error condition, you must initialize the controller. Attempt to correct any underlying
problem(s) that could cause the error condition before beginning the procedure.
Procedure
1. Using Datamate (Base or Advanced), go to the All Points Report.
2. Select Point 99 and right click.
3. Choose Properties.
4. Reset the value of Point 99 to 0.
5. Release Point 99.
If an error condition reappears in the display, repeat the initialization procedure. If the error recurs
after initializing the controller a second time, contact your local Siemens Building Technologies
representative.