Operating Instructions
Table Of Contents
- Table of Contents
- How To Use This Manual
- Chapter 1—Hardware
- Chapter 2—Applications for ATEC— Base VAV
- Chapter 3—Applications for ATEC—VAV with Reheat
- Chapter Overview
- Introduction
- Application 2500: VAV Cooling Only
- Application 2501: VAV Cooling or Heating
- Application 2522: VAV with Electric Reheat or Baseboard Radiation
- Application 2523: VAV with Hot Water Reheat (only one reheat valve)
- Application 2524: VAV Series Fan Powered with One Stage of Electric Reheat
- Application 2526: VAV Parallel Fan Powered with One Stage of Electric Reheat
- Application 2473: Slave Mode
- Chapter 4—Point Database
- Chapter 5—Troubleshooting
- Glossary
- Index
Glossary
Glossary-4 Siemens Building Technologies, Inc.
PID
Proportional plus Integral plus Derivative gain. Functionality used in state-of-the-art control
systems to decrease the response time of the overall control process. The addition of the
derivative gain function to PI control results in the controller providing a control output signal
that is proportional to the rate by which the error is changing. Instead of the control output
merely being proportional to the error (as with proportional only type control), the magnitude
of the control output is significantly increased or decreased to reduce the time needed to
attain the desired setpoint.
PPCL
Powers Process Control Language. Programming language used to write control programs
for building control and energy management functions. PPCL consists of various types of
statements, each performing a different task. These statements become ordered instructions
called control programs that are executed at the field panel. These control programs instruct
the field panel on how to perform calculations, evaluate control strategies, performed time
based actions, and command points.
reheat coil
Hot water, steam, or electric coil located at a branch of a HVAC system that supplies air to an
individual room or zone. Reheat coils are commonly used to allow each room or zone served
by a primary air handling unit to add just as much heat as necessary to satisfy the individual
zone's comfort or ambient temperature needs.
RTS
Room Temperature Sensor.
SI units
Système International d'Unités. The international metric system.
slave mode
Default application that comes up when power is first applied to a Terminal Equipment
Controller.
slope
Factor that converts analog values (used by the controller) to a form that the user can
understand (engineering units). Change in y value (engineering units) per unit change in x
value (analog value). Slope and intercept constants are determined by the type of field
input/output represented by the physical or virtual point.