Operating Instructions

Application 2520: VAV Cooling Only
Siemens Building Technologies, Inc. 2-3
Application 2520: VAV Cooling Only
Overview
In Application 2520, the controller modulates the supply air damper of the terminal box for
cooling. In order for it to work properly, the central Air Handling Unit must provide cool supply
air. See Figure 2-1 and Figure 2-2.
9
0
9
0
4
5
SUPPLY
AIR
3 TO 5 STRAIGHT DUCT
DIAMETERS REQUIRED
FOR PROPER SENSOR READING
AIR
VELOCITY
SENSOR
HI/LO Tubing
Connections
ATEC
24VAC
SUPPLY AIR
DAMPER
FLN
RTS
TEC0421R1