Application 2521: VAV Cooling or Heating
Siemens Building Technologies, Inc. 2-17
Application Notes
1. If temperature swings in the room are excessive or there is trouble maintaining the
setpoint, the cooling loop, the heating loop, or both need to be tuned. If FLOW (Point 75)
is oscillating while FLOW STPT (Point 93 is constant, the flow loop requires tuning.
Contact your local Siemens Building Technologies representative for more information.
2. The ATEC, as shipped from the factory, keeps all associated equipment off. The
controller and its equipment are released to application control at start-up.
Wiring Diagram
The point wiring for Application 2521 is shown in Figure 2-6.
Lo
Hi
24 Vac
FLN
RTS
90
90
4
5
TEC0419R1
Figure 2-6. Application 2521 Wiring Diagram.