Operating Instructions

Chapter 2—Applications for ATEC—Base VAV
2-22 Siemens Building Technologies, Inc.
Point Database
Table 2-5. Point Database for Application 2486.
Point
Number
Descriptor Factory
Default
(SI Units)
Eng. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
01 CTLR ADDRESS 99 1 0
02 APPLICATION 2486 1 0
{03} CHK STATUS -1 1 -1
{04} ROOM TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25
(0.14)
48.0
(8.88888)
– –
{10} CHK OUT NO – YES NO
{13} RM STPT DIAL 74.0
(23.44888)
DEG F
(DEG C)
0.25
(0.14)
48.0
(8.88888)
– –
{19} DI OVRD SW OFF ON OFF
{29} DAY.NGT DAY NIGHT DAY
{35} AIR VOLUME 0 (0.0) CFM (LPS) 4 (1.8876) 0
36 FLOW COEFF 1.0 0.01 0.0
{41} DO 1 OFF ON OFF
{42} DO 2 OFF ON OFF
{48} MTR1 COMD 0.0 PCT 0.4 0.0
{49} MTR1 POS 0.0 PCT 0.4 0.0
51 MTR1 TIMING 95 SEC 1 0
56 DPR1 ROT ANG 90 1 0
58 MTR SETUP 0 1 0
59 DO DIR. REV 0 1 0
{94} CAL AIR NO YES NO
95 CAL SETUP 4 1 0
96 CAL TIMER 12 HRS 1 0
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0.0 –
{99} ERROR STATUS 0 1 0
1. Points not listed are not used in this application.
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.