Operating Instructions

Application 2500: VAV Cooling Only
Siemens Building Technologies, Inc. 3-5
Ordering Notes
Actuating Terminal Equipment Controller with Reheat—Electronic Output
Single unit 550-405
10-pack 550-405P10
Contact your local Siemens Building Technologies, Inc., representative for additional product
numbers.
Autozero module (optional)
Temperature sensor (select one)
Terminal Equipment Controller room temperature sensor
Duct temperature sensor, 10K
, TEC (return-duct sensor)
4-inch (10.2 cm) 540-128
18-inch (46 cm) 540-739
Sequence of Operation
Control Temperature Setpoints
Depending on the controller’s current operational mode (day or night), CTL STPT (Point 92)
holds the value of one of the following setpoints:
Day Mode—CTL STPT holds the value of DAY CLG STPT (Point 6). If the room temperature
sensor has a setpoint dial and STPT DIAL (Point 14) is set to YES, CTL STPT holds the
value of RM STPT DIAL (Point 13).
If the setpoint dial is used and the value of RM STPT DIAL is less than the value of RM STPT
MIN (Point 11), CTL STPT holds the value of RM STPT MIN. If the value of RM STPT DIAL is
greater than the value of RM STPT MAX (Point 12), CTL STPT holds the value of RM STPT
MAX.
Night Mode—CTL STPT holds the value of NGT CLG STPT (Point 8).
NOTE: The value of CTL TEMP (Point 78) is the same as ROOM TEMP (Point 4), unless
CTL TEMP is overridden.
Day and Night Modes
The day/night status of the space is determined by the status of DAY.NGT (Point 29). The
control of this point differs depending on whether the controller is monitoring the status of a
wall switch or is connected to a field panel.
When a wall switch is physically connected to the controller at the AI/DI port labeled “AI 4”
(Figure 3-1 on page 3-3 and Figure 3-3 on page 3-9), and WALL SWITCH (Point 18) is set to
YES, the controller monitors the status of DI 4 (Point 24). When DI 4 is ON (the switch is
closed), DAY.NGT is set to DAY indicating that the controller is in day mode. When DI 4 is
OFF (the switch is open), DAY.NGT is set to NIGHT indicating that the controller is in night
mode.