Application 2501: VAV Cooling or Heating
Overview
In Application 2501, the controller modulates the supply air damper of the terminal box for
cooling and heating. In order for it to work properly, the central air-handling unit must provide
cool supply air in cooling mode and warm air in heating mode. See Figure 3-4 and Figure 3-5.
Wall Switch
(Opt.)
DO3
DO4
AI3
AI4
NO
9
0
9
0
4
5
SUPPLY
AIR
3 TO 5 STRAIGHT DUCT
DIAMETERS REQUIRED
FOR PROPER SENSOR READING
AIR
VELOCITY
SENSOR
HI/LO Tubing
Connections
ATEC
24VAC
SUPPLY AIR
DAMPER
FLN
RTS
TEC2501CDR1
Spare DO
Autozero Module
(Opt.)
Figure 3-4. Application 2501 Control Drawing.