Operating Instructions

Chapter 3—Applications for ATEC—VAV with Reheat
3-24 Siemens Building Technologies, Inc.
Application 2522: VAV with Electric Reheat or
Baseboard Radiation
Overview
In Application 2522, the controller modulates the supply air damper of the terminal box for
cooling and controls stages of electric reheat or baseboard radiation for heating. When in
heating, the terminal box either maintains minimum airflow or modulates the supply air
damper. In order for the terminal box to work properly, the central air-handling unit must
provide supply air. See Figure 3-7 through Figure 3-10.