Operating Instructions

Application 2522: VAV with Electric Reheat or Baseboard Radiation
Siemens Building Technologies, Inc. 3-35
Wiring Diagram
The point wiring for Application 2522 is shown in Figure 3-11.
CAUTION:
The controller’s DOs control 24 Vac loads only. The maximum rating is 12 VA for
each DO. Use an interposing relay for any of the following:
VA requirements higher than the maximum
110 or 220 Vac requirements
DC power requirements
Separate transformers used to power the load
Lo
Hi
24 Vac
FLN
90
90
4
5
TEC2522WDR2
654321
Electric Heat Stage 1 or
Baseboard Heat
Electric Heat Stage 2 or
Autozero Module (Opt.)
Spare AI (100K Thermistor) or
Spare DI (Dry contact closure only)
Wall Switch or
Spare AI (100K Thermistor) or
Spare DI (Dry contact closure only)
RTS
DO3
C
DO4
AI3
C
AI4
BST/FLN LED
Figure 3-11. Application 2522 Wiring Diagram.