Operating Instructions

Application 2522: VAV with Electric Reheat or Baseboard Radiation
Siemens Building Technologies, Inc. 3-39
Table 3-6. Point Database for Application 2522.
Point
Number
Descriptor Factory
Default
(SI Units)
Eng.
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text Off Text
95 CAL SETUP 4 1 0
96 CAL TIMER 12 HRS 1 0
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0.0 –
98 LOOP TIME 5 SEC 1 0
{99} ERROR STATUS 0 1 0
1. Points not listed are not used in this application
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.