Operating Instructions

Chapter 3—Applications for ATEC—VAV with Reheat
3-40 Siemens Building Technologies, Inc.
Application 2523: VAV with Hot Water Reheat (only
one reheat valve)
Overview
In Application 2523, the controller modulates the supply air damper of the terminal box for
cooling and modulates a reheat valve for heating. When in heating, the terminal box either
maintains minimum airflow or modulates the supply air damper. In order for the terminal box
to work properly, the central air-handling unit must provide supply air. See Figure 3-12
through Figure 3-14.
Reheat Valve
DO3
DO4
AI3
AI4
NO
9
0
9
0
4
5
SUPPLY
AIR
3 TO 5 STRAIGHT DUCT
DIAMETERS REQUIRED
FOR PROPER SENSOR READING
AIR
VELOCITY
SENSOR
HI/LO Tubing
Connections
ATEC
24VAC
SUPPLY AIR
DAMPER
FLN
RTS
TEC2523CDR1
Reheat
Coil
Wall Switch (Opt.)
Spare AI/DI
Figure 3-12. Application 2523 Control Drawing.