Application 2523: VAV with Hot Water Reheat (only one reheat valve)
Siemens Building Technologies, Inc. 3-51
Table 3-8. Point Database for Application 2523.
Point
Number
Descriptor Factory
Default
(SI Units)
Eng.
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text Off Text
64 CLG I GAIN 0.01
(0.018)
– 0.001
(0.0018)
0.0 –
65 CLG D GAIN 0 (0.0) 2 (3.6) 0
66 CLG BIAS 0.0 PCT 0.4 0.0
67 HTG P GAIN 10.0 (18.0) 0.25 (0.45) 0.0
68 HTG I GAIN 0.01
(0.018)
– 0.001
(0.0018)
0.0 –
69 HTG D GAIN 0 (0.0) 2 (3.6) 0
70 HTG BIAS 0.0 PCT 0.4 0.0
71 FLOW P GAIN 0.0 0.05 0.0
72 FLOW I GAIN 0.01 0.001 0.0
73 FLOW D GAIN 0 2 0
74 FLOW BIAS 50.0 PCT 0.4 0.0
{75} FLOW 0.0 PCT 0.25 0.0
{76} CTL FLOW MIN 220
(103.818)
CFM
(LPS)
4
(1.8876)
0 –
{77} CTL FLOW MAX 2200
(1038.18)
CFM
(LPS)
4
(1.8876)
0 –
{78} CTL TEMP 74.0
(23.44888)
DEG F
(DEG C)
0.25
(0.14)
48.0
(8.88888)
– –
{79} CLG LOOPOUT 0.0 PCT 0.4 0.0
{80} HTG LOOPOUT 0.0 PCT 0.4 0.0
85 SWITCH LIMIT 5.2 PCT 0.4 0.0
86 SWITCH TIME 10 MIN 1 0 – –
90 SWITCH DBAND 1.0
(0.56)
DEG F
(DEG C)
0.25
(0.14)
0.0 –
{92} CTL STPT 74.0
(23.44888)
DEG F
(DEG C)
0.25
(0.14)
48.0
(8.88888)
– –
{93} FLOW STPT 0.0 PCT 0.25 0.0
{94} CAL AIR NO YES NO
95 CAL SETUP 4 – 1 0 –
96 CAL TIMER 12 HRS 1 0
1. Points not listed are not used in this application
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.
Continued on next page…