Chapter 3—Applications for ATEC—VAV with Reheat
3-52 Siemens Building Technologies, Inc.
Table 3-8. Point Database for Application 2523.
Point
Number
Descriptor Factory
Default
(SI Units)
Eng.
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text Off Text
97 DUCT AREA 1.0
(0.09292)
SQ. FT
(SQ M)
0.025
(0.002323)
0.0 – –
98 LOOP TIME 5 SEC 1 0 – –
{99} ERROR STATUS 0 – 1 0 – –
1. Points not listed are not used in this application
2. A single value in a column means that the value is the same in English units and in SI units.
3. Point numbers that appear in brackets { } may be unbundled at the field panel.