Application 2524: VAV Series Fan Powered with One Stage of Electric Reheat
Siemens Building Technologies, Inc. 3-53
Application 2524: VAV Series Fan Powered with One
Stage of Electric Reheat
Overview
In Application 2524, the controller modulates the supply air damper of the terminal box for
cooling and controls one stage of electric reheat for heating. When in heating, the terminal
box either maintains minimum airflow or modulates the supply air damper. The terminal box
also has a series fan for air circulation. In order for the terminal box to work properly, the
central air-handling unit must provide supply air. See Figure 3-16 through Figure 3-18.
RECIRCULATED
PLENUM AIR
SUPPLY
AIR
SUPPLY AIR
DAMPER
BACKDRAFT
DAMPER
TEC2524CDR3
1 STAGE
ELECTRIC
REHEAT
* 1
AIR VELOCITY
SENSOR
3 TO 5 STRAIGHT DUCT
DIAMETERS REQUIRED FOR
PROPER SENSOR READING
FAN
9
0
9
0
4
5
HI/LO Tubing
Connections
ATEC
24VAC
FLN
Stage 1 Heat
Fan
Spare AI/DI
Wall Switch (Opt.)
DO3
DO4
AI3
AI4
NO
RTS
SAFETIES
BY
OTHERS
1. Heat must be on the outlet.
Figure 3-16. Application 2524 Control Drawing.