Siemens Building Technologies, Inc. 3-43
EMSET (Emergency, set value)
Unitary pre-APOGEE APOGEE BACnet
Syntax
EMSET(value,pt1,...,pt15)
value Value to which points are commanded.
This value can be a decimal, integer, point name, or
local variable.
pt1
through
pt15
Point name to be set to the specified value with emergency
priority.
This parameter can be a LAI or LAO point.
Use
Changes output points to a new value with emergency priority.
A maximum of 15 points can be changed with one EMSET
command.
See also
EMAUTO, EMFAST, EMOFF, EMON, EMSLOW
APOGEE PPCL User’s Manual
3-44 Siemens Building Technologies, Inc.
EMSLOW (Emergency, Slow status)
Unitary pre-APOGEE APOGEE BACnet
Syntax
EMSLOW(pt1,...,pt16)
pt1
through
pt16
Point name to be set to SLOW status with emergency priority.
This parameter can be a LFSSL or LFSSP point.
Use
Changes the operational status of a FAST/SLOW/ STOP point to
SLOW with emergency priority.
A maximum of 16 points can be changed with one EMSLOW
command.
See also
EMAUTO, EMFAST, EMOFF, EMON, EMSET