User Guide

Table Of Contents
Command Syntax
Siemens Building Technologies, Inc. 3-63
INITTO (Initialize totalized value)
Unitary pre-APOGEE APOGEE BACnet
Syntax
INITTO(value,pt1,...,pt15)
value The new value which replaces the current totalized values for
all specified points.
This value can be a decimal, point name, or local
variable. Integers are not allowed.
pt1
through
pt15
Names of points that are defined for totalization. Points must
reside in the same device as the control program.
Use
Change the totalized value of a point to a new value (generally 0).
A maximum of 15 point names can receive the new value through
one INITTO command.
Example
10 IF (DAYOFM.EQ.1.0) THEN INITTO(0.0, PMP1,PMP2)
Notes
Points must reside in the same device as the command.
The INITTO command cannot reset the value of LPACI point
types.
Only points that are defined to be totalized can be initialized by
this command.
When used in APOGEE field panels (which can totalize individual
states of a point), INITTO will reset all totalized states of a digital
point to zero.
APOGEE PPCL User’s Manual
3-64 Siemens Building Technologies, Inc.
LLIMIT (Low limit)
Unitary pre-APOGEE APOGEE BACnet
Syntax
LLIMIT(value,pt1,...,pt15)
value New value to which the low limit is set.
This value can be a decimal, point name, or local
variable. Integers are not allowed.
pt1
through
pt15
Logical names of analog points whose low limits are changed
to the new value. Points must reside in the same device as
the command.
Use
Sets a new low alarm limit for alarmable analog points.
A maximum of 15 points can be set to the same low limit with one
LLIMIT command.
Example
100 IF (OATEMP.GT.68.0) THEN LLIMIT(76.0,
ROOM16) ELSE LLIMIT(68.0,ROOM16)
Notes
Points must reside in the same device as the program.
Points used in the LLIMIT command must be defined as
alarmable.
See also
ALARM, DISALM, ENALM, HLIMIT, NORMAL