User Guide
Table Of Contents
- Table of Contents
- How to Use This Manual
- Chapter 1–Program Methodology
- Overview
- Introduction to PPCL
- PPCL Rules
- PPCL Program Design Guidelines
- Relational Operators
- Logical Operators
- Arithmetic Operators
- Arithmetic Functions
- Special Functions
- Order of Precedence
- Resident Points
- Local Variables
- Point Priority Overview
- At (@) Priority Status Indicators
- Point Status Indicators
- Converting a Sequence of Operation intoProgram Code
- Chapter 2–Control OptionComparisons
- Chapter 3–Command Syntax
- Overview
- ACT (Activate lines)
- ADAPTM (Adaptive control, multiple)
- ADAPTS (Adaptive control, single)
- ALARM (Alarm state)
- AUTO (Auto status)
- DAY (Day mode)
- DBSWIT (Dead band switch)
- DC (Duty cycle)
- DCR (Duty cycle routine)
- DEACT (Deactivate lines)
- DEFINE (Define abbreviation)
- DISABL (Disable lines)
- DISALM (Disable alarm)
- DISCOV (Disable COV)
- DPHONE (Disable phone)
- EMAUTO (Emergency, Auto status)
- EMFAST (Emergency, Fast status)
- EMOFF (Emergency, Off status)
- EMON (Emergency, On status)
- EMSET (Emergency, set value)
- EMSLOW (Emergency, Slow status)
- ENABLE (Enable lines)
- ENALM (Enable alarm)
- ENCOV (Enable COV)
- EPHONE (Enable phone)
- FAST (Fast status)
- GOSUB (Go to subroutine)
- GOTO (Go to line)
- HLIMIT (High limit)
- HOLIDA (Holiday)
- IF/THEN and IF/THEN/ELSE (Conditional control)
- INITTO (Initialize totalized value)
- LLIMIT (Low limit)
- LOCAL (Local variable)
- LOOP (Loop control)
- MAX (Maximum value)
- MIN (Minimum value)
- NIGHT (Night mode)
- NORMAL (Normal operating mode)
- OFF (Off status)
- OIP (Operator interface program)
- ON (On status)
- ONPWRT (On after power return)
- PDL (Peak demand limiting)
- PDLDAT (PDL, define load attributes)
- PDLDPG (PDL, digital point group)
- PDLMTR (PDL, meter monitor)
- PDLSET (PDL, setpoints)
- RELEAS (Release)
- RETURN (Return/end subroutine)
- SAMPLE (Sample a statement)
- SET (Set point value)
- SLOW (Slow status)
- SSTO (Start/stop time optimization)
- SSTOCO (SSTO coefficients)
- STATE (State text command)
- TABLE (Table of coordinates)
- TIMAVG (Average over time)
- TOD (Time of day, digital points)
- TODMOD (TOD modes)
- TODSET (Time of day, analog points)
- WAIT (Wait time)
- Overview
- Glossary
- Appendix A—PPCL Reserved WordList
- Index
Command Syntax
Siemens Building Technologies, Inc. 3-117
Use
The WAIT command turns a point ON or OFF based on the trigger
point switching ON or OFF. Selection of trigger/result action is based
on the mode you enter.
Example
70 C WHEN CNPUMP IS TURNED ON,
72 C THE FIELD PANEL WAITS 60 SECONDS
74 C BEFORE TURNING CHPUMP ON.
75 WAIT(60,CNPUMP,CHPUMP,11)
76 ON(CNPUMP)
Notes
• The position of the WAIT statement in a program affects its
operation. The WAIT statement only works if it sees a change of
value (COV) through both states for the trigger point.
• On a return from power failure or when the WAIT command is
enabled, the trigger point must be toggled before the command
executes regardless of the current state of either pt1 or pt2.
• The command to pt2 is only issued once during the normal
operation of the program until triggered again.
APOGEE PPCL User’s Manual
3-118 Siemens Building Technologies, Inc.