Alarm priority (ALMPRI)
Unitary pre-APOGEE APOGEE BACnet
Syntax
ALMPRI(pt1)
pt1 A point name for which the current alarm priority is taken.
Use
Accesses the alarm priority level of a point defined in an enhanced
alarming control strategy. The value of ALMPRI can range from 1
through 6. Besides testing ALMPRI for a specific value, you can also
assign the value of ALMPRI to another point.
Example 1
230 C
232 C THIS LINE TESTS IF THE POINT CALLED
234 C RMTEMP IS AT ALARM PRIORITY LEVEL 1.
236 C
240 IF (ALMPRI(RMTEMP).EQ.1) THEN ON (OPBELL)
Example 2
330 C
332 C THIS LINE ASSIGNS THE ALARM PRIORITY LEVEL
334 C OF RMTEMP TO THE POINT CALLED TMPPRI.
336 C
340 TMPPRI = ALMPRI(RMTEMP)
Notes
ALMPRI must reside in the same field panel as the point on which
the function is being performed.
For BACnet firmware, the ALMPRI value corresponds to a priority in
the Notification class for the point’s current alarm state. Table 1-4
outlines the BACnet Notification classes and shows how they relate
to the APOGEE ALMPRI values.
APOGEE PPCL User’s Manual
1-40 Siemens Building Technologies, Inc.
Table 1-4. APOGEE to BACnet
Notification Class Reference.
ALMPRI Value
BACnet
Notification Class
1 0-31
2 32-63
3 64-95
4 96-127
5 128-191
6 192-255