User Guide

Table Of Contents
Command Syntax
Siemens Building Technologies, Inc. 3-7
The ADAPTM damper time constant parameter entry (in
seconds) is calculated using this formula:
tcd = T
downstream coils
+ T
sensor
+ T
damper actuator
Where:
tcd = ADAPTM damper time constant parameter entry (in
seconds)
T
downstream coils
= time constants of coils alone downstream of
dampers (between the dampers and the duct temperature
sensor).
T
sensor
= time constant of the supply air sensor (usually about
30 seconds)
T
damper actuator
= stroke time of the damper actuator (often 30
seconds)
Example
The AHU has mixed air dampers, a heating coil, and a cooling
coil.
The heating coil alone has a 5 second time constant. The
cooling coil alone has a 20 second time constant. The supply
air temperature sensor time constant is 30 seconds. The
damper actuator stroke time is 30 seconds. Therefore, the
damper time constant is:
Heating coil time constant: 5 seconds
Cooling coil time constant: 20
Supply air temp. sensor: 30
Damper actuator: 30
Total 85 seconds
APOGEE PPCL User’s Manual
3-8 Siemens Building Technologies, Inc.
tch Heating time constant (seconds).
This parameter can be a point name, local variable
name, or decimal number.
This value must be greater than or equal to 3 times the
st value.
For applications with dampers and cooling only (no
heating), set tch to the value of tcd.
The time constant of the heating coil alone is calculated using
the following formula:
maxwaterhot
maxair
max
max
coilheating
/L
/L
15.0
GPM
CFM
0.02T
s
s
==
Where:
CFM
max
= Maximum or design airflow rate in cubic feet per
minute
GPM
max
= Maximum or design hot water flow rate in gallons per
minute
l/s
air max
= Maximum or design air flow rate in liters per second
l/s
hot water max
= Maximum or design hot water flow rate in liters
per second
The ADAPTM heating time constant parameter entry (in
seconds) is calculated using this formula:
tch = T
heating coil
+ T
downstream coils
+ T
sensor
+ T
hcactuator
Where:
tch = ADAPTM heating time constant parameter (in seconds).
T
downstream coils
= time constants of other coils alone
downstream of heating coil (between heating coil and duct
temperature sensor).
T
sensor
= time constant of the supply air sensor (usually about
30 seconds).
T
hc actuator
= stroke time of the heating coil actuator (often 30
seconds).
Example
An AHU has a design CFM of 50000 and the design flow
through the heating coil is 465 gpm. The heating coil valve has